Technical Article

National Electrical Code Basics: Computing Voltage Drop in Branch Circuits and Feeders Part 2

August 02, 2022 by Lorenzo Mari

Learn more formulas to calculate voltage drops in single-phase branch circuits and feeders.

To catch up on the rest of Lorenzo Mari's series on computing voltage drop in branch circuits and feeders, follow these links:

Some approximate methods suitable to calculate DC voltage drops may apply to AC circuits with small loads, reasonably short, and closely spaced conductors. These methods ignore the effect of line reactance. Yet, its impact on the results may be less than other factors encountered in simple wiring calculations.

 

Image used courtesy of Pixabay

 

The Circular Mil

The circular mil (CM) is a measure of the conductor’s cross-sectional area. Figure 1 shows the actual cross-sectional area of a circular conductor A = ΠD²/4 = 3.1416 x D²/4.

 

Figure 1. Conductor cross-section. Image used courtesy of Lorenzo Mari

 

Finding the area in circular mils requires the diameter in mils.

1 mil = 1/1 000 inch = 10ˉ³ inch (in)

By definition, the cross-sectional area of a conductor with a diameter D = 1 mil is 1 CM.

If D = 1 mil, then A = 1 CM = 3.1416 x D²/4 = 3.1416 x ¼ = 0.7854 square mils (sq mils)

sq mils = 0.7854 x CM

CM = 1/0.7854 x sq mils = 1.2732 x sq. mils

Pick a conductor with D = N mils (N = any positive number).

A = 0.7854 x N² sq. mils

CM = 1.2732 x 0.7854 x N² = N²

Then, the area in circular mils of any conductor equals the diameter in mils squared.

ACM = D²

The area in mm² is

Amm² = ΠD²/4 = 0.7854 x D²

Where D = diameter in mm.

 

NEC Table 8

NEC Table 8 displays standard conductor sizes. It sizes conductors from 18 to 4/0 AWG (American Wire Gage) and from 250 to 2 000 kcmil, copper (uncoated and coated), and aluminum. Sizes 18 to 8 AWG include solid round and stranded conductors. Among other data, Table 8 indicates the cross-sectional area in circular mils, mm², and in.².

Table 8 also contains the conductor DC resistance at 75°C. The NEC’s resistance, reactance, and impedance values are line-to-neutral or ohm-to-neutral.

 

Example 1.

Find the conductor size of a solid conductor with a diameter of 0.1285 in.

0.1285 in. = 128.5 mil

ACM = D² = 128.5² = 16 512

 

Table 8 shows CM  = 16 510 for size N° 8 AWG.

This problem may be solved by looking for a diameter of 0.128 in. in the column Overall Diameter in Table 8. Observe that overall diameters for stranded conductors are higher than for solid conductors.

 

Example 2.

Calculate the cross-sectional area in mm² for the conductor in example 1.

D = 0.1285 in x 25.4 mm/in = 3.264 mm

Amm² = 0.7854 x D² = 0.7854 x 3.264² = 8.367 mm²

Table 8 shows an area of 8.367 mm² for a solid conductor N° 8 AWG.

 

A Formula for Computing Voltage Drop

A typical formula to compute approximate voltage drop in single-phase circuits is

VD = 2 x ρ x I x L / A

 

where: 

A = cross-sectional area of the conductor in CM or mm².

ρ = resistivity of the wire material in Ω CM/ft or Ω mm²/m. ρ is the resistance of a conductor 1 foot long, a cross-sectional area of 1 CM or a conductor 1 m long, and a cross-sectional area of 1 mm² – recall that R = ρL/A.

 I = load current (A).

VD = voltage drop (V).

 L = distance from source to load in feet or meters.

The constant 2 contemplates the return conductor from the load to the source.

To determine the size of wire that will produce a specific voltage drop, transpose the formula to read

A = 2 x ρ x I x L / VD

Some references state these formulas as

VD = 2 x K x I x L / A

A = 2 x K x I x L / VD

Where K is the conductor resistivity.

 

Voltage Drop Formulas in English and Metric Units

The resistivity of commercial hard-drawn copper wire at 25°C is 10.895 Ω CM/ft or 0.018113 Ω mm²/m.

The resistivity of commercial aluminum wire at 25°C is 17.345 Ω CM/ft or 0.028834 Ω mm²/m.

It is vital to ponder that the resistance of copper and aluminum increases with temperature due to the augmented molecular movement. The material constants in the following formulas will change with temperature.

English units

2 x K = 2 x 10.895 Ω CM/ft = 21.79 Ω CM/ft

CM = 21.79 Ω CM/ft x I(A) x L(ft) / VD(V) for copper

2 x K = 2 x 17.345 Ω CM/ft = 34.69 Ω cmil/ft

CM = 34.69 Ω CM/ft x I(A) x L(ft) / VD((V) for aluminum

To compute K for every conductor, multiply circular mils by the resistance per foot according to NEC Table 8.

K = CM x Ω/ft = Ω CM/ft

Table 1 shows an average value of K = 12.873 Ω CM/ft considering copper conductors ( Direct-Current Resistance at 75°C).

 

Size 

AWG or kcmil

CM

RDC

(Ω/kft)

(Stranded)

K

(Ω CM/ft)

12

6 530

1.98

12.929

10

10 380

1.24

12.871

8

16 510

0.778

12.845

6

26 240

0.491

12.884

4

41 740

0.308

12.856

3

52 620

0.245

12.892

2

66 360

0.194

12.874

1

83 690

0.154

12.888

1/0

105 600

0.122

12.883

2/0

133 100

0.0967

12.871

3/0

167 800

0.0766

12.853

4/0

211 600

0.0608

12.865

250

250 000

0.0515

12.875

300

300 000

0.0429

12.870

350

350 000

0.0367

12.845

400

400 000

0.0321

12.840

500

500 000

0.0258

12.900

Average

 

 

12.873

Table 1. The average value of K derived from NEC Table 8 data (Copper conductors).

 

The equation for single-phase circuits using the average value of K will be

2 x K = 2 x 12.873 = 25.746

CM = 25.75 Ω CM/ft x I(A) x L(ft) / VD(V) for copper at 75°C

Table 2 shows an average value of K = 21.182 Ω CM/ft with aluminum conductors.

 

Size 

AWG or kcmil

CM

RDC

(Ω/kft)

(Stranded)

K

(Ω CM/ft)

12

6 530

3.25

21.223

10

10 380

2.04

21.175

8

16 510

1.28

21.133

6

26 240

0.808

21.202

4

41 740

0.508

21.204

3

52 620

0.403

21.206

2

66 360

0.319

21.169

1

83 690

0.253

21.174

1/0

105 600

0.201

21.226

2/0

133 100

0.159

21.163

3/0

167 800

0.126

21.143

4/0

211 600

0.100

21.160

250

250 000

0.0847

21.175

300

300 000

0.0707

21.210

350

350 000

0.0605

21.175

400

400 000

0.0529

21.160

500

500 000

0.0424

21.200

Average

 

 

21.182

Table 2. The average value of K derived from NEC Table 8 data (Aluminum conductors).

 

The equation for single-phase circuits using the average value of K will be

2 x K = 2 x 21.182 = 42.364

CM = 42.36 Ω CM/ft x I(A) x L(ft)/VD(V) for aluminum at 75°C

 

Metric units

Following a similar procedure (at 25°C) for single-phase circuits leads to

2 x K = 2 x 0.018113 Ω mm²/m = 0.03623 Ω mm²/m

A(mm²) = 0.03623 Ω mm²/m x I(A) x L(m) / VD(V) for copper, and

2 x K = 2 x 0.028834 Ω mm²/m = 0.05767 Ω mm²/m

A (mm²) =  0.05767 Ω mm²/m x I(A) x L(m) / VD(V) for aluminum

Rather than computing an average value of K for copper at 75°C, let’s calculate K only for a conductor of 500 kcmil, with data from NEC Table 8.

K = 253 mm² x 0.0845 Ω/km /1 000  = 0.021379 Ω mm²/m

2 x K = 2 x 0.021379 Ω mm²/m = 0.04276 Ω mm²/m

A =  0.04276 Ω mm²/m x I(A) x L(m) / VD(V) for copper

Computing K for a conductor of 500 kcmil, aluminum, at 75°C, with data from NEC Table 8.

K = 253 mm² x 0.1391 Ω/km/1 000  = 0.035192 Ω mm²/m

2 x K = 2 x 0.035 Ω mm²/m = 0.07038 Ω mm²/m

A =  0.07038 Ω mm²/m x I(A) x L(m) / VD(V) for aluminum

 

Formula With Shared English and Metric Units

The following formula combines English and Metric units for copper conductors at 25°C in single-phase circuits.

CM = 70.86 x I(A) x L(m) / VD(V)

These approximate formulas apply to DC and AC circuits with a high power factor, preferably 100%, as is usually the case in residential electrical installations.

Voltage drop calculations in commercial and industrial electrical installations typically require formulas using impedance rather than resistance. Applying the formulas to AC circuits with low power factor loads and significant line reactance may lead to substantial error.

Example 3.

In the circuit of figure 2

 

Figure 2. 240V, 2-wire, single-phase circuit. Image used courtesy of Lorenzo Mari

 

a. Find VD in volt and percentage using English units, at 25°C.

NEC Table 8 shows 26 240 circular mils for conductor N° 6 AWG.

VD = 21.79 Ω CM/ft x 60 A x 55 ft / 26 240 = 2.74 V

VD = (2.74 V/240 V) * 100 = 1.14%

b. Find the receiving-end voltage VR.

VR = Vs – VD

VR = 240 V – 2.74 V = 237.26 V

Example 4.

Repeat example 1 using Metric units at 25°C.

a.

NEC Table 8 shows 13.30 mm² for conductor N° 6 AWG.

50 ft x 0.3048 m/ft = 16.764 m

VD= 0.03623 Ω mm²/m x 60 A x 16.764 m / 13.30 mm² = 2.74 V.

VD = (2.74 V/240 V) * 100 = 1.14%

b.

VR = Vs – VD

VR = 240 V – 2.74 V = 237.26 V

Example 5.

Compute VD in example 1 using the English/Metric formula.

VD = 70.86 x 60A x 16.764 m/26 240 = 2.72 V.

 

Voltage Drop Tables

There is no need to apply the voltage drop formulas every time. Although there is a lot of software on this subject, it is always practical to have some tables at hand to make quick estimates.

It is vital to understand the basis of the table, such as the formula used, single- or multiple-phase, number of wires, conductor material, AC or DC, magnetic or nonmagnetic conduit, ambient temperature, power factor, and frequency.

Table 3 shows voltage drops for copper conductors according to the formula

VD(V) = 25.75 Ω CM/ft x I(A) x L(ft) / CM, for copper at 75°C

This table uses the Ampere-feet method. The product I(A) x L(ft) becomes a constant read as follows: increasing the current and decreasing the distance in the same proportion, and vice versa, keeps VD constant.

 

Conductor Size

300

250

4/0

3/0

2/0

1/0

1

Ampere-feet

 

 

 

 

 

 

 

200,000

17.17

20.60

24.34

30.69

38.69

48.77

61.54

100,000

8.58

10.30

12.17

15.35

19.35

24.38

30.77

90,000

7.73

9.27

10.95

13.81

17.41

21.95

27.69

80,000

6.87

8.24

9.74

12.28

15.48

19.51

24.61

70,000

6.01

7.21

8.52

10.74

13.54

17.07

21.54

60,000

5.15

6.18

7.30

9.21

11.61

14.63

18.46

30,000

2.58

3.09

3.65

4.60

5.80

7.32

9.23

25,000

2.15

2.58

3.04

3.84

4.84

6.10

7.69

20,000

1.72

2.06

2.43

3.07

3.87

4.88

6.15

10,000

0.86

1.03

1.22

1.53

1.93

2.44

3.08

5,000

0.43

0.52

0.61

0.77

0.97

1.22

1.54

4,000

0.34

0.41

0.49

0.61

0.77

0.98

1.23

3,000

0.26

0.31

0.37

0.46

0.58

0.73

0.92

2,000

0.17

0.21

0.24

0.31

0.39

0.49

0.62

1,000

0.09

0.10

0.12

0.15

0.19

0.24

0.31

900

0.08

0.09

0.11

0.14

0.17

0.22

0.28

800

0.07

0.08

0.10

0.12

0.15

0.20

0.25

700

0.06

0.07

0.09

0.11

0.14

0.17

0.22

600

0.05

0.06

0.07

0.09

0.12

0.15

0.18

500

0.04

0.05

0.06

0.08

0.10

0.12

0.15

Table 3. Voltage drop for copper conductors in a nonmagnetic conduit. Single-phase, 2-wire, and 3-wire, 100% power factor, 60Hz.

 

Ampere-feet = I(A) x L(ft)

VD(V) = 25.75 Ω x Ampere-feet / CM

Example 6.

Figure 3 shows a 120/240V, 3-wire, single-phase feeder supplying a lighting panel with a 23 kW balanced load. Using Table 3, compute the copper conductor size required for a maximum line-to-line voltage drop of 2% if the run length is 250 ft.

 

Figure 3. 120/240 V, 3-wire, single-phase circuit supplying lighting load. Image used courtesy of Lorenzo Mari

 

I = 23 kW/240 V = 95.83 A

L = 250 ft

95.83 A x 250 ft = 23,958 A-ft, say 24,000 A-ft

Maximum VD allowed = 240 x 0.02 = 4.8 V

Table 3 shows VD = 4.88 V in the crossing of the 20,000 A-ft line and size 1/0 column, above the VD required.

VD = 4.84 V in the crossing of the 25,000 A-ft line and size 2/0 column, with a margin of 1,000 A-ft. 

Interpolating between 3.87 V (20,000 A-ft) and 4.84 V (25,000 A-ft), the actual VD = 4.64 V (24,000 A-ft) = 1.93%, below the VD required.

Use size N° 2/0 conductors.

Another way to solve the problem with Table 3.

Try size 2/0

24,000 A-ft = 20,000 A-ft + 4,000 A-ft

VD at 20,000 A-ft = 3.87 V

VD at 4,000 A-ft = 0.77 V

Total VD = 3.87 V + 0.77 V = 4.64 V = 1.93%

Use size N° 2/0 conductors.

There are similar tables employing the Ampere-meter method.

 

Summary

The CM defines a cross-sectional area. One circular mil is the area of a circle with a diameter of 1 mil.

Another expression of the cross-sectional area of a conductor is square millimeters (mm²).

NEC Table 8 provides a good deal of conductor data.

Several formulas allow voltage drop calculations with approximate results in simple circuits. These formulas are helpful in DC circuits and AC circuits with negligible line reactance and high power factor loads.

For most purposes, it is unnecessary to use formulas to determine wire sizes. There are many tables available to do quick calculations. Knowing the basis of the table employed to avoid miscalculations is vital.

 

Feature image used courtesy of Pixabay