National Electrical Code Basics: Computing Voltage Drop in Branch Circuits and Feeders Part 3
Learn about voltage drop calculations in three-phase branch circuits and feeders.
To catch up on the rest of Lorenzo Mari's series on computing voltage drop in branch circuits and feeders, follow these links:
- National Electrical Code Basics: Computing Voltage Drop in Branch Circuits and Feeders Part 1
- National Electrical Code Basics: Computing Voltage Drop in Branch Circuits and Feeders Part 2
Using Single-phase Voltage Drop Formulas and Tables in Three-phase Systems
Reducing the I²R losses and voltage drops in three-phase systems allows the use of smaller conductors, decreasing the weight of copper or aluminum required.
The formulas and tables employed to compute voltage drops in single-phase systems may be used in three-phase systems through multiplication by factors. The elaboration of these factors requires a review of a few three-phase basics.
Voltages in Balanced Three-phase Systems
Synchronous generators in utility power plants produce most of the power transmitted and distributed through lines operating as three-phase circuits.
These generators produce three sinusoidal voltages, with equal Root Medium Squared (RMS) magnitude and a phase shift of 120 electrical degrees among them. Since the voltages are sinusoidal, their representation uses phasors.
The system is balanced because they have equal RMS magnitudes. There are no unbalanced generators under normal operating conditions.
The three generated voltages can be connected either in a wye configuration or a delta configuration. The wye connection is typical in utility generators. Figure 1 shows both formats.
Figure 1. Balanced 3-phase voltage sources wye- and delta-connected. Image used courtesy of Lorenzo Mari
The Wye Connection
In the wye connection (figure 1a), three source terminals form a common node labeled the neutral (N).
The line-to-neutral system voltages, or phase voltages, are equal to the individual source voltages
VAN = E 0ے°
\[V_{BN} = Eے-120° V\]
\[V_{CN}= Eے120° V\]
To determine the line-to-line voltages or line voltages, we apply the Kirchhoff Voltage Law (KVL)
\[V_{AB} = V_{AN} – V_{BN} = Eے0° - Eے-120° = √3Eے30° V\]
\[V_{BC} = V_{BN} – V_{CN} = Eے-120° - Eے120° = √3Eے270° V\]
\[V_{CA} = V_{CN} – V_{AN} = Eے120° - Eے0° = √3Eے150° V\]
Denoting the magnitude of the line voltage by VL and the phase voltage by VP, we have
VL = √3 VP
In the wye connection, the line voltage magnitude is √3 times the phase voltage. There is phase displacement between the line and phase voltages.
The Delta Connection
We get a delta connection by joining the three sources in series (figure 1b). The generator neutral is absent since the three sources do not have a common point. For instance, no line-to-neutral voltages exist, except for the line-to-ground capacitance (not covered in this analysis).
In the delta connection, the line voltages are equal to the individual phase voltages, as follows
\[V_{AB} = Eے0° V\]
\[V_{BC} = Eے-120° V\]
\[V_{CA} = Eے120° V\]
Then
VL = VP
Currents in Balanced Three-phase Loads
Figure 2 shows a generator’s three single-phase loads connected to phases A, B, and C.
Figure 2. Single-phase loads connected to a generator. Image used courtesy of Lorenzo Mari
The three single-phase circuits have the currents IL1, IL2, and IL3, flowing from the source to the load and back to the source – assuming wye connected generator windings with the neutral connection accessible. Each neutral will carry current, and the single-phase voltage drop formulas will apply.
Similar to the sources, the three single-phase loads may be connected in wye or delta configurations (figure 3).
Figure 3. 3-phase loads wye- and delta-connected. Image used courtesy of Lorenzo Mari
The Wye-wye Connection
Figure 3a shows the three loads connected in wye. The term wye-wye means that the source and the load are wye-connected.
The voltages applied to the loads are equal to the source phase voltages.
The three impedances are equal in a balanced system. Assuming load impedances Z1 = Z2 = Z3 = ZP ےθ, Ohm’s law, gives the following phase currents
\[I_{A} = V_{AN}/Z_{P} ےθ = Eے0°/Z_{P} ےθ A\]
\[I_{B} = V_{BN}/Z_{P} ےθ = Eے-120°/Z_{P} ےθ A\]
\[I_{C} = V_{CN}/Z_{P} ےθ = V_{CN} = Eے120°/Z_{P} ےθ A\]
The currents in the three phases have the same magnitude and 120° phase displacement among them.
In each phase of a wye-wye connection, the line current equals the phase current in magnitude and phase. Denoting the magnitude of the line current by IL and the phase current by IP, we have
IL = IP = I
Applying Kirchhoff’s current law (KCL)
IN = IA + IB + IC = 0
The neutral current is zero in a wye-connected, balanced, three-phase system. Since the neutral carries no current in this symmetrical circuit, it may be ignored to establish a three-phase, three-wire system – although it is physically a four-wire system.
In our discussion about voltage drops, it is essential to have the circuit operating under balanced conditions. As a result, only one conductor feeds every load, producing only half the voltage drop that would occur under unbalanced conditions – with the phase and neutral carrying current.
The Wye-delta Connection
Figure 3b shows the three balanced loads connected in delta. The voltages applied to the loads are equal to the source line voltages. Systems with delta-connected loads are three-wire because there is no neutral connection.
The system is wye-delta or delta-delta depending on the source connection – wye- or delta-connected. Delta-connected sources are atypical, so we will adopt a wye-connected source.
Assuming load impedances Z1 = Z2 = Z3 = ZP ےθ, the phase currents are
\[I_{L1} = V_{AB}/ Z_{P} ےθ = √3Eے30°/Z_{P} ےθ A\]
\[I_{L2} = V_{BC}/ Z_{P} ےθ = √3Eے270°/Z_{P} ےθ A\]
\[I_{L3} = V_{CA}/ Z_{P} ےθ = √3Eے150°/Z_{P} ےθ A\]
With three like impedances, this is a balanced load with equal phase current magnitudes, displaced 120°.
Applying KCL to determine the line currents IA, IB, and IC
IA = IL1 – IL3
IB = IL2 – IL1
IC = IL3 – IL2
After some calculations we get
\[I_{A} = √3 I_{L1}ے-30° A\]
\[I_{B} = √3 I_{L2}ے-30° A\]
\[I_{C} = √3 I_{L3}ے-30° A\]
Then
IL = √3 IP
We conclude that the line current magnitude equals √3 times the magnitude of the phase current, and the line current lags 30° the phase current, assuming a positive sequence.
Multiplying Factors
Recall the typical formula to compute approximate voltage drop in single-phase circuits
VD = 2 x K x IL x L / A
where
VD = voltage drop
K = conductor resistivity
IL = line current (IL= IP in a single-phase circuit)
A = cross-sectional area of the conductor
L = distance from source to load
The constant 2 contemplates the return conductor from the load to the source
The criteria to find the multiplying factors are
a. The constant 2 should be removed since there is no return conductor (neutral) in delta-connected loads and balanced wye-connected loads – they are three-wire circuits.
b. In a delta-connected load IL = √3 IP. Substitute IL by √3 IP in the formula. With VD based on VL, the factor is √3/2 = 0.866.
c. In a wye-connected load, VL = √3 VP.
c1. With VD based on VL, divide VD by √3, and the factor is √3/2 = 0.866.
c2. With VD based on VP, the factor is ½ = 0.5.
To summarize, in three-phase systems, multiply the single-phase result by 0.866 if using line voltages and by 0.5 if using phase voltages.
Example 1
Figure 4 shows a branch circuit supplying a delta-connected, low inductance load. Compute the three-phase voltage drop using the following single-phase formula for aluminum.
VD = 2 x 17.35 Ω CM/ft x IL(A) x L(ft) /CM
Figure 4. Balanced 3-phase delta-connected load. Image used courtesy of Lorenzo Mari
IP = 240 V/41.6 Ω = 5.77 A
IL = √3 IP = 10 A
The NEC Table 8 shows 6 530 circular mils for conductor size N° 12 AWG.
VD = (2 x 17.35 Ω CM/ft x 10 A x 100 ft / 6 530) x 0.866 = 4.6 V
Example 2
Figure 5 shows a branch circuit supplying a wye-connected, low inductance load. Compute the size of copper wire for a voltage drop not higher than 1% based on VP. Use the following single-phase formula for copper
CM = 2 x 10.895 Ω CM/ft x I(A) x L(ft) /VD(V)
Figure 5. Balanced 3-phase wye-connected load. Image used courtesy of Lorenzo Mari
I = 277 V/18.47 Ω = 15 A
VD = 0.01 x 277 V = 2.77 V
CM = (2 x 10.895 Ω CM/ft x 15 A x 200 ft / 2.77 V) x 0.5 = 11 800
The NEC Table 8 shows 10 830 CM for N° 10 AWG and 16 510 for N° 8 AWG. Use N° 8 AWG.
Example 3
Repeat example 2 for a voltage drop not higher than 1% based on VL.
I = 277 V/18.47 Ω = 15 A
VD = 0.01 x 480 V = 4.8 V
CM = (2 x 10.895 Ω CM/ft x 15 A x 200 ft / 4.8 V) x 0.866 = 11 800
Use N° 8 AWG.
The Proportional Method to Compute Voltage Drops
The following expressions are helpful to compute the voltage drop and phase shift due to the voltage drop along the conductors
VR = VS x ZL/ZS
where
VR = phase voltage at the load
VS = phase voltage at the source
ZL = load impedance
ZS = system impedance, including ZL
All quantities expressed phasorially
The magnitude of the voltage drop is
ƖVDƖ = ƖVSƖ – ƖVRƖ
Example 4
Figure 6 shows a source supplying power to an apparatus with a power factor different from 100%.
Figure 6. Source feeding an apparatus. Image used courtesy of Lorenzo Mari
a. Compute ZL in polar form.
The format for the polar form is
ƖZLƖ ےθ
ƖZLƖ = √(12² + 9²) = 15 Ω
θ = tan¯¹ 9/12 = tan¯¹ 0.75 = 36.9°
\[Z_{L} = 15 ے36.9° Ω\]
b. Compute ZS in rectangular and polar forms.
The format for the rectangular form is
ZS = R + jX
ZS = 1 + j0 + 12 + j9 = 13 + j9 Ω
ƖZSƖ = √(13² + 9²) = 15.81 Ω
θ = tan¯¹ 9/13 = tan¯¹ 0.69 = 34.7°
\[Z_{S} = 15.81ے 34.7° Ω\]
c. Compute the voltage at the load. Select VS as the reference.
\[V_{R} = 480 ے0° \times 15 ے36.9°/15.81ے 34.7° = 455.4 ے2.2° V\]
d. Compute the voltage drop magnitude in volt and percentage.
ƖVDƖ = 480 V – 455.4 V = 24.6 V
24.6 V/480 V x 100 = 5.13%
e. What’s the phase shift introduced by the conductor?
2.2°
f. Compute the apparatus load factor.
P.F. = cos θ = cos 36.9° = 0.8 = 80% lagging
A Typical Approximate Formula Used in Three-phase Circuits
Only one phase is required to determine the voltage drop in a three-phase system operating under balanced conditions. The phasor diagram of figure 7 shows the single-phase voltages at the source, the load, and the conductor (closing the loop).
Figure 7. Single-phase phasor diagram for voltage drop calculations. Image used courtesy of Lorenzo Mari
The projection of the conductor voltage on the real axis approximates the voltage drop magnitude. The result is
ƖVDƖ = I (R cos θ + X sin θ)
where
ƖVDƖ = magnitude of line-to-neutral voltage drop
I = magnitude of line current
R = conductor resistance
X = conductor reactance
θ = load angle
cos θ = load power factor
sin θ = load reactive factor
The formula error lessens as the angle Φ approximates zero – the formula is exact for Φ = 0. In practice, the angle Φ is small.
Modifying this equation to calculate the voltage drop in percentage directly, we get
VD% = kVA (R cos θ + X sin θ) /10 kV²
where
VD% = voltage drop in percentage
kVA = three-phase apparent power
kV = line voltage
Notice that kVA and kV are three-phase values.
Example 5
a. Using the approximate formula and the results of example 4, compute the voltage drop magnitude in the figure 6 circuit.
\[I = 480 Vے0°/15.81ے34.7° = 30.36ے-34.7° A\]
The magnitude of line current = 30.36 A
ZL angle = θ = 36.9°
R = conductor resistance = 1 Ω
X = conductor reactance = 0 Ω
cos θ = load power factor = 0.8
sin θ = load reactive factor = 0.6
ƖVDƖ = 30.36 x (1 x 0.8 + 0 x 0.6) = 24.29 V
b. Calculate the percent voltage drop.
24.29 V/480 V x 100 = 5.06%
c. Calculate the voltage drop in percentage directly.
Apparent power = 30.36 A x 0.48 kV = 14.57 kVA
VD% = 14.57 (1 cos 36.9° + 0 sin 36.9°) /10 x 0.48² = 5.06%
Example 6
A three-phase underground cable supplies power to a balanced inductive load (lagging power factor). System data are as follows
Cable impedance ZC = 0.0771 + j0.0724 Ω/phase
Load impedance ZL = 13.75 + j10.31 = 17.19 ے36.86° Ω/phase
Source voltage 4.16Y/2.4 kV
a. Determine the voltage drop using the proportional method.
VR = VS x ZL/ZS
\[Z_{S} = Z_{C} + Z_{L} = 0.0771 + 13.75 + j(0.0724 + 10.31) = 13.83 + j10.38 = 17.29
ے36.9° Ω/phase\]
Selecting the phase voltage as the reference
\[V_{S} = 2 400 ے0° V\]
\[V_{R} = 2 400 ے0° \times 17.19 ے36.86°/ 17.29 ے36.9° = 2 385.4 ے-0.04°\]
\[ƖVDƖ = 2 400 V – 2 385.4 V = 14.6 V\]
\[14.6 V/ 2 400 V x 100 = 0.61%\]
b. Determine the voltage drop using the approximate formula.
ƖVDƖ = I (R cos θ + X sin θ)
ZL angle = θ = 36.86°
R = conductor resistance = 0.0771 Ω
X = conductor reactance = 0.0724 Ω
cos θ = load power factor = 0.8
sin θ = load reactive factor = 0.6
\[I = V_{S}/Z_{S} = 2 400 ے0° /17.29 ے36.9° = 138.72 ے-36.9° A\]
The magnitude of line current = 138.72 A
ƖVDƖ = 138.72 (0.0771 x 0.8 + 0.0724 x 0.6) = 8.56 + 6.03 = 14.6 V
c. Calculate the voltage drop in percentage directly.
VD% = kVA (R cos θ + X sin θ) /10 kV²
Line voltage = VL = 4.16 kV
3-phase kVA = √3 x VL x I = √3 x 4.16 kV x 138.72 A = 1 000 kVA
VD% = 1 000 (0.0771 x 0.8 + 0.0724 x 0.6) / 10 x 4.16² = 0.61%
Summary
Large residential complexes and commercial and industrial facilities employ three-phase systems to supply significant power.
The application of factors allows single-phase methods to calculate voltage drops in three-phase systems.
This article reviews some typical methods to determine voltage drops in three-phase systems.
Featured image used courtesy of Pexels